Mitsubishi MGPEZ-140VJA Ducted Air Conditioner, 14.0 kW, Three-Phase 380 V
The PRO series was designed to offer the most competitive inverter solution, meeting the most fundamental market needs. With the same compact design as its superior Standard Inverter model and almost all of its features, it is the most competitive solution for all types of residential and commercial applications. Available in single-phase (71/100/125/140) and three-phase (100/125/140) voltages, for 1x1 split units only.
The Power Inverter series is designed to achieve high seasonal energy performance, thanks to the new compressor design and the use of the latest energy-saving technologies, achieving high performance ratings of A+ or A++ in both cooling and heating in most categories.
Increased maximum cooling distances up to 100 m of total piping.
Improved energy efficiency, up to A++.
Optional motor to achieve 30 Pa of external static pressure (100/125/140).
100% of rated heating capacity down to -3°C.
Improved performance (ZRP(ZM)100/125/140)
The new outdoor models (100/125/140) offer improved energy efficiency, by an average of 5%, compared to the previous version. In addition, their weight has been slightly reduced and they are compatible with the "Dual Set Point" function.
The Power Inverter series allows for a distance of up to 100 m (100/125/140 models), which, combined with a vertical distance of 30 meters, facilitates installation. Advanced Energy-Saving Technologies
High-Efficiency Fan and New Grille
The shape of the outdoor unit's fan and grille has been redesigned to optimize airflow and heat exchange, while maintaining the same noise level.
High-Efficiency Heat Exchanger: 100-125-140
The tube diameter has been reduced from 9.52 to 7.94 mm, allowing the number of coil stacks to be increased from 52 to 64. This, combined with a larger heat exchange surface area, improves the efficiency of the heat exchange process.
Capacity
Nominal Cooling (min.-max.): 13.1 (6.1-14.1)
Nominal Heating (min.-max.): 15 (4.2-15.8)
Cooling: 11,530 kcal/h
Heating: 12,900 kcal/h
Nominal Consumption:
Cooling: 4.96 kW
Heating: 4.28 kW
Energy Efficiency Ratio
EER/COP: 2.70/3.50
SEER (label): 210.1%
SCOP (label): 150.2%
Indoor Unit
Heating (intermediate climate zone)
Airflow (low/medium/high): 32.0/39.0/46.0 m3/min. Static pressure: 35/50/70/100/150 Pa
Sound level (low/medium/high): 34/38/43 dB
Sound power: 67 dB
Outdoor unit
Airflow: 86 m3/min
Sound level: 55 dB(A)
Sound power: 73 dB(A)
Dimensions: H x W x D: 981 x 1050 x 330 (+40) mm
Weight: 84 kg
R32 refrigerant: 3.60/675/2.43 kg/GWP/TCO2 eq
Voltage/Phase - Maximum current: Three-phase 380 V
Liquid/gas pipe diameter: 9.52/15.88 mm
Maximum vertical/total pipe length: 30/40 m Operating range:
Outdoor temperature for cooling: -15 to +46°C.
Outdoor temperature for heating: -10 to +21°C.
Indoor unit dimensions H x W x D: 250 x 1,600 x 732 mm
Weight: 44 kg
Outdoor unit dimensions H x W x D: 981 x 1,050 x 330 +40 mm.
Weight: 84 kg